PlcConsole
Data Logger Manual · Analysis

Data explorer & export

Choose the graph that answers your question, inspect the evidence behind a result and share or export the original readings.

Choose measurements and a period

  1. Open Choose measurements or Edit points. Narrow the list by site, PLC and collection or search by point name.
  2. Confirm the source, register and unit. Identical names can appear on different PLCs. Use Include former point definitions to find removed or replaced points when their history is still accessible.
  3. Apply the selection and set a period. Use a relative window for the latest readings, Today or Yesterday for a calendar day in your display time zone, or Custom period for exact boundaries.
  4. Read the displayed interval. The start is inclusive and the end exclusive, so observations at a shared boundary belong to the following window. The period arrows move the window. Calendar days can span 23 or 25 hours during a daylight-saving change.

On a phone, period controls stack vertically. Tap the relevant date or time field to open its picker. Use the on-screen Apply and Cancel controls to commit or discard the edit.

Graph reference

Choose a graph that answers the question

The View selector shows compatible options for the points you selected. Charts take up to four points. Export supports a larger selection.

ViewChoose it whenRead the result
Over time · numeric trendFind when Temperature R0 spiked or compare it with Pressure R1 over the same period. Different units use separate charts.The horizontal axis is time. Hover or tap an actual sample for its reading and observation timestamp. Errors, gaps and scaling changes can break the line. Use stepped lines when the displayed value should stay visually level between recorded changes.
Over time · Boolean timelineFind when the pump alarm was ON, OFF or unknown. Switch to recorded Boolean values to inspect individual 0/1 readings.Read the coloured intervals and their actual start, end and duration. Unknown intervals can follow a failed or expired reading. They provide no evidence of an OFF state.
Compare values · barsCompare compatible points over one period, or compare the same points across time buckets. Select either numeric points or Boolean points.Numeric metrics are minimum, maximum and time-weighted average. Boolean metrics are observed ON duration and ON percentage. Check coverage and partial-bucket labels before comparing bars.
Value distribution · histogramCheck which ranges occur most often for one numeric point. For Temperature R0, look for a cluster around its usual level or a second cluster from another operating condition.Each bin counts valid recorded samples in a value range. The overlay shows its bounds, count and share of included samples. More frequent sampling can increase the count without increasing the time spent in that range.
State time shares · doughnutUnder Over time, select State time shares for one Boolean point. Use the timeline when you need to know when each state occurred.Each segment is a share of evaluated time, including unknown duration. Read its duration and percentage together. Future time is outside the evaluated total.
Relationship (XY) · scatter plotExplore how two numeric points from the same PLC vary together. For example, select Temperature R0 and Pressure R1 to see which pairs occur in the demo.One axis is assigned to each point. The latest eligible Y observation at or before X must still be valid and within the lag limit. Inspect both observation times. Repeated pairs can overlap at one plotted position, and swapping axes can change the pairs.
  • Comparison buckets. Fixed buckets start at the selected start time. Calendar-day buckets follow local midnight in the calculation time zone. A partial first or last bucket and incomplete coverage within a bucket describe different things.
  • Time-weighted average. Readings contribute according to how long they remain valid. A value of 10 held for 20 seconds and 40 held for 30 seconds gives an average of 28. Unknown time lowers coverage and is excluded from the average.
  • Historical conversion. A change to scaling or unit can split a comparison into separate groups or require you to choose a recorded interpretation for a histogram or XY plot. Keep the interpretations separate when explaining the result.
  • XY lag and pairing. Set Maximum lag to 0 seconds if you need identical observation timestamps. With automatic tolerance, Logger uses the historical collection intervals and a 30-second ceiling. When pairs overlap, compare the paired-measurement count with the distinct-position count and inspect individual pairs.
  • Change of selection. If the current graph becomes incompatible, Data explorer returns to Over time and keeps your points and period. A mixed numeric and Boolean selection offers Over time only.
Time-period comparison

Compare numeric or Boolean measurements over time

Use Time periods to compare one or more points across successive buckets. Use Compare points to compare their values across one full selected period.

  1. Choose one to four numeric points or one to four Boolean points. A comparison uses one kind at a time. To see numeric and Boolean series together on a time axis, use Over time.
  2. Choose Compare values → Time periods. Select the period and a Time step of 1, 5 or 15 minutes, 1 hour or calendar day. Fixed steps start at the selected From time. Calendar days use local midnight and can be shorter or longer on a daylight-saving transition.
  3. Choose Value to compare. For a numeric measurement such as Temperature R0, use minimum or maximum to find the extremes, or time-weighted average to compare typical values over known time. Different units, such as °C and bar, appear in separate chart groups.
  4. For a Boolean measurement such as Pump alarm M0, choose Observed ON duration to compare the seconds spent ON or ON share of evaluated time for a percentage. That percentage includes unknown time in the denominator. Read coverage alongside it.
  5. Hover or tap a bucket to read the value and actual interval. Check coverage, incomplete data and partial time buckets before comparing bars. No data means there is insufficient evidence for the calculation. A zero can be a valid result, such as good observations showing the alarm stayed OFF.
Example. In a five-minute bucket, 30 seconds known ON gives 30 seconds of ON duration and an ON share of 10%. If another 120 seconds are unknown, coverage is 60%. The chart can quantify the observed ON time, while the gap limits what you can infer about the rest of the bucket.

Use a time trend or Boolean timeline for the exact moment a value or state changed. Period bars answer a different question by summarising each bucket.

Boolean measurements

Tell when a state changed and how long it lasted

  1. Select Pump alarm M0 alone and choose Over time → State timeline. Check the source name before reading the chart. ON is the state of the alarm bit in this example.
  2. Inspect an interval to read its state, start, end and duration. If an interval is Unknown, open Data details to check for a read error, an expired observation or another gap. Use the recorded-values option when you need the exact sequence of 0/1 samples.
  3. Switch to State time shares to answer how much of the evaluated period was ON, OFF or unknown. The labels show duration and percentage. For example, 30 seconds ON, 30 OFF and 60 unknown produce shares of 25%, 25% and 50% across two minutes.
Read the two views together. Equal ON durations can come from one long interval or several short ones. Use the timeline to tell them apart and the shares chart to quantify exposure across the same window.
Numeric relationships

Check which temperature and pressure values occurred together

  1. Choose Temperature R0 and Pressure R1 from the same PLC, set a period with readings for both, and select Relationship (XY).
  2. Set the X-axis anchor and check both units. Use Swap X and Y to reverse the question. If the period contains a scaling change, choose which recorded interpretation to compare for each affected axis.
  3. Inspect a marker to read both values and their individual timestamps. Use the pair inspection controls when several observations overlap at the same position. Compare pair count with distinct-position count before interpreting the spread.
  4. If you see few or no pairs, check the available period, point quality and Maximum lag. An eligible Y reading must be at or before X and still valid. A higher lag limit cannot revive an expired or failed reading.

A cluster shows the combinations recorded together in this period. It gives you a reason to investigate those time windows. To learn which quantity changed first, return to Over time and compare the timestamps.

Inspect a result and its coverage

Hover to preview a reading, bar, bin, state interval or pair. Click or tap to hold that selection while reading Details and inspection. Keyboard arrows move among observations or chart items. Escape closes the preview.

Open Data details · quality and diagnostics to distinguish the count of valid samples, the duration with usable readings and failed attempts. Check Measured at for the actual observation time. A blank interval is missing evidence. A measured zero is a valid value.

Export or share the investigation

  1. Confirm the selected measurements and period. Select Export and choose Excel (.xlsx) for spreadsheet review or CSV for importing into analysis tools. An export accepts up to 32 points, 31 days, 250,000 samples and 64 MiB. Split dense exports by time or point selection.
  2. Read each row as one stored sample of one point. Check the observation timestamp, received timestamp, quality, unit and historical conversion. Failed attempts can have empty values. A gap without a recorded attempt creates no row.
  3. Use Copy link to this view to share the points, graph type and exact period. A relative period becomes fixed in the link. The recipient needs access to the underlying measurements, and the view is recalculated from retained observations.
Check the result. You can identify the same source and measurement times in the exported rows. Exploring and exporting use stored data.