Collection

Create a scheduled read, activate it and verify that its values reach stored history.

Choose the PLC and points

In PLC overview, use the intended PLC’s Configurations action. You can also use the PLC filter on the Configurations page and select New configuration.

  1. Confirm the site and PLC in the editor. Name the configuration and set the read interval. Respect the minimum enforced by the Remote environment.
  2. In Add a register or range, choose the family, starting address, value count and data type. Select Add points to add the definitions.
  3. Name the individual points and set their units. Use Interpretation and conversion only when the PLC register map calls for scaling, an offset or a different word or byte order.
Point definitions

Turn a register reading into a measurement

A point combines a register address, a stored data type and a physical meaning. Use the PLC register map to decide which type to select. Use the family and starting address to locate the value, and the count to add successive values of the selected type.

  • Boolean points. Use a Boolean point for a two-state signal such as Pump alarm M0. Its history supports state timelines and time shares, and rules can react to valid TRUE or FALSE readings.
  • Numeric points. Match the register width and signedness or floating-point encoding to the PLC. Check byte and word order where the selected type exposes them. Give each point a name and unit that a dashboard reader will recognise.
  • Scaling. The stored engineering value uses raw value × multiplier + offset. If the PLC stores pressure as tenths of a bar, a multiplier of 0.1 and an offset of 0 turn a raw 40 into 4 bar. Verify the result against a known reading before using it in a rule.
  • Edits and history. Review the new version in the editor when the register definition or conversion changes. Retained readings keep their original interpretation. Revisit affected alerts before treating the new values as comparable.

After Add points, scroll to Points. Use Name for a label that will make sense in dashboards and notifications, check the register and Type, and enter the engineering Unit. Expand Interpretation and conversion on a numeric point to check byte or word order, multiplier and offset. The example preview shows how decoding and scaling work before you save the definition.

Activate and verify collection

  1. Choose Save configuration. A new configuration starts paused.
  2. Choose Activate on the saved row and open Run status.
  3. Check the current state and Last successful measurement. Scheduled means the collection is active and waiting for its next slot. Open Last run to see the measurements and timestamps from the most recent reported run.
  4. If you see Retry scheduled, Reading failed or Waiting for agent, check the notice and expand Technical diagnostics for the reported reason, next slot and available version evidence. A previous successful timestamp can remain visible while a new run is waiting or failing.
  5. Open Data explorer and use a period covering the successful observation. Check that the same point and timestamp are present in stored history.
Check the result. A successful run and a matching stored measurement confirm the end-to-end path. A saved configuration or a connected agent alone confirms only one step.

Pause or retire a configuration

Use Pause to suspend a configuration you intend to resume. Wait for confirmation of the actual state, especially if an agent was offline when you requested the change. Archive only when you intend to retire the configuration. Prior measurements remain available according to retention and access permissions.

For an agent that has not applied the request or returned any values, follow Site Agents & troubleshooting.